Transformer Pump & Fan Monitoring unit. Automatic system exercising and status indication.
Automatic weekly or monthly system exercising
Monitors pump & fan operation during exercising and normal operation
Indicates individual pump and fan failure
12 monitored inputs (2 pump, 10 fan)
2 voltage free 8 Am p changeover control relays
3 voltage free 8 Am p changeover relays providing status information
Watchdog alarm relay for power failure
Universal input power supply
Integral battery back up for memory retention
LCD for set up and fault identification
Can be retrofitted to existing installations
On site fitting service available
Download this specification sheet as a PDF
Technical Specification
Configuration:
Inputs:
Up to 12 current sensing inputs from monitoring transducers
2 Pumpd & 10 Fan inputs
16 button keypad for 'step by step' set-up procedure
User optional password protection for settings
Outputs:
Indications:
System working
Identified fault condition
Test condition and status
A voltage free 'Watchdog' contact for power failure
Functions:
Electric current status motoring
System programmable by time and date
System test button
Typical Applications:
Pumps & Fans monitoring
Motor operation monitoring
Programmable exercising
Case:
Polycarbonate - rated to IP54
Dimensions:
H-230mm, W-220mm, D-126mm
Case entry:
-rear 20mm 'knock-outs'
-bottom blank for customer drilling
Mounting:
Surface mounted
Power:
Supply Voltage:
85 - 264Vac @ 47 - 440Hz
110 - 340VDC
Power supply fuse protected
Trickle charge battery back-up retains switch settings and time/date data in excess of 300 days
Electrical Connections:
2.5mm² PCB mounted terminal blocks with detachable plugs in easily accessed compartment
Switch Configurations:
Voltage free Single Pole Double Throw relaysrated at 8A 250Vac, 30VDC
Indication:
Liquid crystal alpha-numeric display providing:
Operating Status
Test Status
Set-up menus
Fault identification
EMC compliance:
Instrument complies with applicable EMC directivesfor radiated emissions and susceptibility, conducted emissions, electrical fast transients and electrostatic discharge
Options:
Mounting bracket for free standing application
Transducers fitted as standard with 5 metres of cable - longer lengths to order